Troubleshooting table
Status Light | Possible Problem | Solution | |
Green The system is getting a distance reading beyond the current setpoints example . Setpoints 5ft | 10ft distance is getting a reading of 20ft | LAC is getting a reading but might be unalighed. try to check what the LAC is seeing and realign. | |
Pulsing Green The system is not getting a return signalexample . Other crane is further then 38ft | not getting a signal but the other crane is closer then the max distance rating | check alignment of sensor to other crane if everthing is level | |
Purple The system is in its first setpointexample . Slow setpoint is set to 10ft and crane is 10ft or closer | other crane is further then the setpoint but still going into slow | check that the senor is not hitting another object. Like a wall column if its mounted close to the rails. 2nd possiblity is the hysterisis hasn’t reached its value yet see note at bottom | |
Light Blue The system is in its 2nd setpoint example . Stop setpoint is set to 10ft and crane is 10ft or closer | other crane is further then the setpoint but still going into stop | check that the senor is not hitting another object. Like a wall column if its mounted close to the rails. 2nd possiblity is the hysterisis hasn’t reached its value yet see note at bottom | |
Red System cant see the sensor | System not working | The Sensor is not talking to the motherboard. The plug could have come undone or the sensor is defective. Replace system | |
No light | System not working | Power supply issue. Or processor is faulty |